Dwell Functions: b6

User parameters for dwell functions are shown in the following table.

„

DROOP Control: b7

User parameters for droop functions are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Fac-

tory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux
Vector

Open

Loop

Vector

2

b6-01

Dwell
Reference
at Start

The dwell function is used to
temporarily hold the frequency
when driving a motor with heavy
load.

0.0

to

400.0

0.0Hz

No

A

A

A

A

A

1B6H

Dwell Ref
@Start

b6-02

Dwell
Time at
Start

0.0

to

10.0

0.0 s

No

A

A

A

A

A

1B7H

Dwell
Time
@Start

b6-03

Dwell
Frequency
at Stop

0.0

to

400.0

0.0Hz

No

A

A

A

A

A

1B8H

Dwell Ref
@Stop

b6-04

Dwell
Time at
Stop

0.0

to

10.0

0.0 s

No

A

A

A

A

A

1B9H

Dwell
Time
@Stop

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b7-01

Droop
Control Level

Sets the speed decrease as a
percentage of motor base
speed (E1-06) when the
motor is at 100% load torque.
Setting of 0.0 disables droop
control.

0.0

to

100.0

0.0%

Yes

No

No

No

A

A

1CAH

Droop
Quantity

b7-02

Droop
Control
Delay Time

Determines the droop control
delay time in response to a
load change.

0.03

to

2.00

0.05 s

Yes

No

No

No

A

A

1CBH

Droop Delay
Time

Run command

Output frequency

Time

ON

b6-03

OFF

b6-01

b6-04

b6-02