Acceleration/deceleration: c1, Autotuning parameters: c – Yaskawa G7 Drive User Manual

Page 133

Advertising
background image

5

-22

‹

Autotuning Parameters: C

The following settings are made with the autotuning parameters (C parameters): Acceleration/deceleration
times, s-curve characteristics, slip compensation, torque compensation, speed control, and carrier frequency
functions.

„

Acceleration/Deceleration: C1

User parameters for acceleration and deceleration times are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f with

PG

Open

Loop

Vector

1

Flux

Vec-tor

Open

Loop

Vector

2

C1-01

Acceleration
Time 1

Sets the time to accelerate
from zero to maximum
frequency.

0.0

to

6000.0

*

10.0 s

Yes

Q

Q

Q

Q

Q

200H

Accel Time 1

C1-02

Deceleration
Time 1

Sets the time to decelerate
from maximum frequency to
zero.

Yes

Q

Q

Q

Q

Q

201H

Decel Time 1

C1-03

Acceleration
Time 2

Sets the time to accelerate
from zero to maximum
frequency when selected via a
multi-function input.

Yes

A

A

A

A

A

202H

Accel Time 2

C1-04

Deceleration
Time 2

Sets the time to decelerate
from maximum frequency to
zero when selected via a
multi-function input.

Yes

A

A

A

A

A

203H

Decel Time 2

C1-05

Acceleration
Time 3

Sets the time to accelerate
from zero to maximum
frequency when selected via a
multi-function input.

No

A

A

A

A

A

204H

Accel Time 3

C1-06

Deceleration
Time 3

Sets the time to decelerate
from maximum frequency to
zero when selected via a
multi-function input.

No

A

A

A

A

A

205H

Decel Time 3

C1-07

Acceleration
Time 4

Sets the time to accelerate
from zero to maximum
frequency when selected via a
multi-function input.

No

A

A

A

A

A

206H

Accel Time 4

C1-08

Deceleration
Time 4

Sets the time to decelerate
from maximum frequency to
zero when selected via a
multi-function input.

No

A

A

A

A

A

207H

Decel Time 4

C1-09

Emergency
Stop Time

Sets the time to decelerate
from maximum frequency to
zero for the multi-function
input "Fast Stop" function.
Note: This parameter is also

used by selecting "Fast
Stop" as a Stop Method
when a fault is detected.

No

A

A

A

A

A

208H

Fast Stop
Time

C1-10

Accel/decel
Time Setting
Unit

Sets the setting resolution of
C1-01 to C1-09:
0: 0.01sec (0.00 to 600.00sec)
1: 0.1sec (0.0 to 6000.0sec)

0 or 1

1

No

A

A

A

A

A

209H

Acc/Dec Units

Advertising