User Parameters Settable in Quick Programming Mode

The minimum user parameters required for Drive operation can be monitored and set in quick programming
mode. The user parameters displayed in quick programming mode are listed in the following table. These, and
all other user parameters, are also displayed in advanced programming mode.

Refer to the overview of modes on page 3-5 for an overview of quick programming mode.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS
Register

Display

V/f

V/f

with

PG

Open

-loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

A1-02

Control
Method
Selection

Selects the Control Method of the Drive.
0: V/F control without PG
1: V/F control with PG
2: Open Loop Vector
3: Flux Vector (Closed Loop Vector)
4: Vector 2 wo/PG
Note: Does not return to factory

setting when drive is initialized.

0 to 4

2

No

Q

Q

Q

Q

Q

102H

Control
Method

b1-01

Frequency
Reference
Selection

Selects the frequency reference input

source.

0: Operator - Digital preset speed U1-

01 or d1-01 to d1-17.

1: Terminals - Analog input terminal

A1 (or terminal A2 based on
parameter H3-09).

2: Serial Com - Modbus RS-422/485

terminals R+, R-, S+, and S-.

3: Option PCB - Option board

connected on 2CN.

4: Pulse Input (Terminal RP)

0 to 4

1

No

Q

Q

Q

Q

Q

180H

Reference
Source

b1-02

Run
Command
Selection

Selects the run command input source.
0: Operator - RUN and STOP keys on

Digital Operator.

1: Terminals - Contact closure on

terminals S1 or S2.

2: Serial Com - Modbus RS-422/485

terminals R+, R-, S+, and S-.

3: Option PCB - Option board

connected on 2CN.

0 to 3

1

No

Q

Q

Q

Q

Q

181H

Run
Source

b1-03

Stopping
Method
Selection

Selects the stopping method when the
run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast with Timer (A new run

command is ignored if received
before the timer expires).

0 to 3

*13

0

No

Q

Q

Q

Q

Q

182H

Stopping
Method

C1-01

Acceleration
Time 1

Sets the time to accelerate from zero to
maximum frequency.

0.0

to

6000.0

*1

10.0 s

Yes

Q

Q

Q

Q

Q

200H

Accel
Time 1

C1-02

Deceleration
Time 1

Sets the time to decelerate from maxi-
mum frequency to zero.

Yes

Q

Q

Q

Q

Q

201H

Decel
Time 1