Pg option setup: f1, Option parameters: f – Yaskawa G7 Drive User Manual

Page 152

Advertising
background image

User Parameter Tables

5-

41

‹

Option Parameters: F

The following settings are made with the option parameters (F parameters): Settings for Option Cards.

„

PG Option Setup: F1

User parameters for the PG Speed Control Card are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

F1-01

PG Parameter Sets the number of pulses per

revolution (PPM) of the
encoder (pulse generator).

0

to

60000

1024

No

No

Q

No

Q

No

380H

PG Pulses/
Rev

F1-02

Operation
Selection at
PG Open
Circuit
(PGO)

Sets stopping method when a

PG open circuit fault (PGO)
occurs. See parameter F1-14.

0: Ramp to stop - Decelerate

to stop using the active
deceleration time.

1: Coast to stop
2: Fast - Stop - Decelerate to

stop using the deceleration
time in C1-09.

3: Alarm Only - Drive

continues operation.

0 to 3

1

No

No

A

No

A

No

381H

PG Fdbk
Loss Sel

F1-03

Operation
Selection at
Overspeed
(OS)

Sets the stopping method
when an overspeed (OS)
fault occurs. See F1-08 and
F1-09.
0: Ramp to stop - Decelerate

to stop using the active
deceleration time.

1: Coast to stop
2: Fast - Stop - Decelerate to

stop using the deceleration
time in C1-09.

3: Alarm Only - Drive

continues operation.

0 to 3

1

No

No

A

No

A

A

382H

PG
Overspeed
Sel

F1-04

Operation
Selection at
Deviation

Sets the stopping method
when a speed deviation
(DEV) fault occurs.
See F1-10 and F1-11.
0: Ramp to stop - Decelerate

to stop using the active
deceleration time.

1: Coast to stop
2: Fast - Stop - Decelerate to

stop using the deceleration
time in C1-09.

3: Alarm Only - Drive

continues operation.

0 to 3

3

No

No

A

No

A

A

383H

PG
Deviation Sel