Wiring Control Circuit Terminals

2-

23

‹

Control Circuit Terminal Functions

The functions of the control circuit terminals are shown in Table 2.10. Use the appropriate terminals for the correct
purposes.

Table 2.10 Control Circuit Terminals

Type

No.

Signal Name

Function

Signal Level

Digital

input

signals

S1

Forward run/stop command

Forward run when CLOSED; stopped when OPEN.

24 Vdc, 8 mA

Photocoupler

isolation

S2

Reverse run/stop command

Reverse run when CLOSED; stopped when OPEN.

S3

Multi-function input 1

*1

Factory setting: External fault when

CLOSED.

Multi-

function

digital

inputs.

Functions

set by

H1-01 to

H1-10

S4

Multi-function input 2

*1

Factory setting: Fault reset when CLOSED.

S5

Multi-function input 3

*1

Factory setting: Multi-speed speed

reference 1 effective when CLOSED.

S6

Multi-function input 4

*1

Factory setting: Multi-speed speed

reference 2 effective when CLOSED.

S7

Multi-function input 5

*1

Factory setting: Jog frequency selected when

CLOSED.

S8

Multi-function input 6

*1

Factory setting: External baseblock when

CLOSED.

S9

Multi-function input 7

*1

Factory setting: Multi-speed speed

reference 3 effective when CLOSED.

S10

Multi-function input 8

*1

Factory setting: Multi-speed speed

reference 4 effective when CLOSED.

S11

Multi-function input 9

*1

Factory setting: Accel/decel time selected

when CLOSED.

S12

Multi-function input 10

*1

Factory setting: Emergency stop

(NO contact) when CLOSED.

SC

Sequence input common

-