Limiting Motor Torque (Torque Limit Function)

The motor torque limit function is enabled only with open-loop torque control.

In the open-loop vector control method, the user-set value is applied to the torque limit by calculating inter-
nally the torque output by the motor. Enable this function if you do not want a torque above a specified
amount to be applied to the load, or if you do not want a regeneration value above a specified amount to occur.

„

Related Parameters

Multi-function Analog Input (H3-05, H3-09)

Note The forward torque limit is the limit value when the analog input signal generates forward torque. This torque limit setting is enabled even when the

analog input signal generates forward torque while the motor is operating (regeneration).

Parame-

ter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L7-01

Forward
Torque
Limit

Sets the torque limit value as a percentage
of the motor rated torque. Four individual
quadrants can be set.

0 to 300

200%

No

No

No

A

A

A

Torq Limit
Fwd

L7-02

Reverse
Torque
Limit

0 to 300

200%

No

No

No

A

A

A

Torq Limit
Rev

L7-03

Forward
Regenera-
tive Torque
Limit

0 to 300

200%

No

No

No

A

A

A

Torq Lmt
Fwd Rgn

L7-04

Reverse
Regenera-
tive Torque
Limit

0 to 300

200%

No

No

No

A

A

A

Torq Lmt
Rev Rgn

Setting

Value

Function

Contents (100%)

Control Methods

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

10

Positive torque limit

Motor's rated torque

No

No

Yes

Yes

Yes

11

Negative torque limit

Motor's rated torque

No

No

Yes

Yes

Yes

12

Regenerative torque limit

Motor's rated torque

No

No

Yes

Yes

Yes

15

Positive/negative torque limit

Motor's rated torque

No

No

Yes

Yes

Yes

Output torque

Positive torque

Reverse

Negative torque

No. of

motor

rotations

Regenerative

state

Regenerative

state