Precautions, Setting precautions, Application precautions – Yaskawa G7 Drive User Manual

Page 293: Hold analog frequency using user-set timing

Advertising
background image

6

-76

‹

Hold Analog Frequency Using User-set Timing

When one of H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selection) is set to 1E
(sample/hold analog frequency command), the analog frequency reference will be held from 100ms after the
terminal is turned ON, and operation will continue thereafter at that frequency.

Fig 6.52 Sample/Hold Analog Frequency

„

Precautions

When setting and executing sample and hold for analog frequency references, observe the following precau-
tions.

Setting Precautions

When using sample/hold of analog frequency reference, you cannot use the following commands at the same
time. If these commands are used at the same time, operation error OPE03 (invalid multi-function input selec-
tion) will occur.

•

Acceleration/Deceleration Ramp Hold command

•

UP/DOWN command

•

Trim Control Increase/Decrease command

Application Precautions

•

When performing sample/hold of analog frequency references, be sure to store references of 100ms mini-
mum. If the reference time is less than 100ms, the frequency reference will not be held.

•

The analog frequency reference that is held will be deleted when the power supply is turned OFF.

‹

Switching Operations between a Communications Option Card and Con-
trol Circuit Terminals

You can switch reference input between the Communications Option Card and the control circuit terminals.
Set one of the parameters H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selection)
to 2 (Option/Drive selection) to enable switching reference input using the terminal ON/OFF status when the
Drive is stopped.

Sample/hold

command

Analog input

Frequency reference

The analog value 100ms after the command is turned ON is used as the frequency reference.