Timer function: b4, Pid control: b5 – Yaskawa G7 Drive User Manual

Page 128

Advertising
background image

User Parameter Tables

5-

17

„

Timer Function: b4

User parameters for timer functions are shown in the following table.

„

PID Control: b5

User parameters for PID control are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b4-01

Timer
Function
ON-delay
Time

Used in conjunction with a
multi-function digital input
and a multi-function digital
output programmed for the
timer function. This sets the
amount of time between when
the digital input is closed, and
the digital output is energized.

0.0

to

3000.0

0.0 s

No

A

A

A

A

A

1A3H

Delay-ON
Timer

b4-02

Timer
Function
OFF-delay
Time

Used in conjunction with a
multi-function digital input
and a multi-function digital
output programmed for the
timer function. This sets the
amount of time the output
stays energized after the
digital input is opened.

0.0

to

3000.0

0.0 s

No

A

A

A

A

A

1A4H

Delay-OFF
Timer

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b5-01

PID Function
Setting

This parameter determines

the function of the PID
control.

0: Disabled
1: D= Feedback
2: D= Feed-Forward
3: Freq. Ref. + PID output

(D = Feedback)

4: Freq. Ref. + PID output

(D = Feed-Forward)

0 to 4

0

No

A

A

A

A

A

1A5H

PID Mode

b5-02

Proportional
Gain Setting

Sets the proportional gain of
the PID controller.

0.00

to

25.00

1.00

Yes

A

A

A

A

A

1A6H

PID Gain

b5-03

Integral Time
Setting

Sets the integral time for the
PID controller. A setting of
zero disables integral control.

0.0

to

360.0

1.0 s

Yes

A

A

A

A

A

1A7H

PID I Time

b5-04

Integral Limit
Setting

Sets the maximum output
possible from the integrator.
Set as a percentage (%) of
maximum frequency.

0.0

to

100.0

100.0%

Yes

A

A

A

A

A

1A8H

PID I Limit

b5-05

Derivative
Time

Sets D-control derivative
time. A setting of 0.00
disables derivative control.

0.00

to

10.00

0.00 s

Yes

A

A

A

A

A

1A9H

PID D Time