Related parameters, Setting precautions – Yaskawa G7 Drive User Manual

Page 275

Advertising
background image

6

-58

„

Related Parameters

*

1

In order for a restart to occur, the run command must be maintained throughout the ride thru period.

*2 Factory settings will vary based on drive capacity (values given here are for 200-240V class, 0.4kW).
*3 Setting value for 200-240V class. Double the value when working with 380-480V class drives

„

.

Setting Precautions

Error output signals are not output during momentary power loss recovery.

To continue Drive operation after power has been restored, make settings so that run commands from the
control main circuit terminal are stored even while power is suspended.

If the momentary power loss operation selection is set to 0 (Disabled), when the momentary power loss
exceeds 15ms during operation, alarm UV1 (main circuit undervoltage) will be detected.

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L2-01

Momentary
Power Loss
Detection
Selection

Enables and disables the

momentary power loss function.

0: Disabled - Drive trips on (UV1)

fault when power is lost.

1: Power Loss Ride Thru
Time - Drive will restart if power

returns within the time set in

L2-02.*

1

2: CPU Power Active - Drive will

restart if power returns prior to
control power supply shut
down.*

1

0 to 2

0

No

A

A

A

A

A

PwrL
Selection

L2-02

Momentary
Power Loss
Ride-thru
Time

Sets the power loss ride-thru time.
This value is dependent on the
capacity of the Drive. Only
effective when L2-01 = 1.

0 to 25.5

0.1sec

*2

No

A

A

A

A

A

PwrL
Ridethru t

L2-03

Momentary
Power Loss
Minimum
Base Block
Time

Sets the minimum time to wait to
allow the residual motor voltage to
decay before the Drive output turns
back on during power loss ride thru.
After a power loss, if L2-03 is
greater than L2-02, operation
resumes after the time set in L2-03.

0.1

to

5.0

0.2sec

*2

No

A

A

A

A

A

PwrL
Baseblock t

L2-04

Momentary
Power Loss
Voltage
Recovery
Ramp Time

Sets the time it takes the output
voltage to return to the preset V/f
pattern after speed search (current
detection mode) is complete.

0.0

to

5.0

0.3sec

*2

No

A

A

A

A

A

PwrL V/F
Ramp t

L2-05

Undervoltage
Detection
Level

Sets the Drive's DC Bus
undervoltage trip level. If this is set
lower than the factory setting,
additional AC input reactance or
DC bus reactance may be necessary.
Consult the factory before changing
this parameter setting.

150

to

210

*3

190Vdc

*3

No

A

A

A

A

A

PUV Det
Level