Yaskawa G7 Drive User Manual

Page 127

Advertising
background image

5

-16

* Factory settings will change when the control method is changed. (Open-loop vector 1 factory settings are given.) Set to “3” in V/f w/PG.

** Factory settings will change when the control method is changed.

b3-05

Speed Sarch
Delay Time

Delays the speed search
operation after a momentary
power loss to allow time for an
external output contactor to
re-energize.

0.0

to

20.0

0.2 s

No

A

A

A

A

A

195H

Search
Delay

b3-10

Speed Sarch
Detection
Compensation
Gain

Sets the gain for the frequency
at which the Drive starts speed
estimation speed search. Use
only when b3-01 = 0 or 1.

1.00

to

1.20

1.10

No

A

No

A

No

A

19AH

Srch Detect
Comp

b3-13

Proportional
Gain of
Observer
During
Speed
Search

Sets n4-08 in units of 1.0 for
P-gain (PI Controls) as the
Observer during Speed Search.
Note: Normally this parameter
need not be changed, although
a low setting is needed when
OV occurs during speed search
with a large amount of load
inertia. Set larger values when
working with speed agree.

0.1

to

2.0

1.0%

No

No

No

No

No

A

19DH

Srch Est P
Gain

b3-14

Bi-directional
Speed
Search
Selection

This parameter enables the
Drive to detect the direction of
rotation of the motor during
speed search.
0: Disable - Drive uses

frequency reference
direction.

1:Enable - Drive uses detected

direction

0 to 1

1

No

A

A

A

No

A

19EH

Bidir Search
Sel

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2