Yaskawa G7 Drive User Manual

Page 151

Advertising
background image

5

-40

* 1. The factory setting depends upon the Drive capacity. The value for a 200-240V class Drive of 0.4 kW is given.
* 2. The setting range is 10% to 200% of the Drive's rated output current. The values for a 200-240V class Drive of 0.4 kW is given.
* 3. If a multi-function input is set for motor 2 (H1-†† = 16), the factory setting will depend upon the Drive capacity. The value for a 200-240V class

Drive of 0.4 kW is given.

E4-09

ASR
Proportional
Gain - Motor 2 Sets the proportional gain for

the speed control loop (ASR.)

0.00

to

300.00

*2

20.00

*

3

Yes

No

A

No

A

A

33FH

ASR P Gain
Mtr2

E4-10

ASR Integral
Time - Motor 2 Sets the speed control loop

(ASR) integral time in seconds.

0.000

to

10.000

0.500s

*

3

Yes

No

A

No

A

A

340H

ASR I Time
Mtr2

E4-11

Torque
Compensation
Gain – Motor 2

Magnifies the torque
compensation gain.
Normally this parameter does
not require change, however
adjustments can be made as
follows:

- When the motor cable is

long, increase the setting.

- When using a motor with a

smaller capacity than the
drive (the largest motor
being used), increase this
setting.

If the motor begins to

vibrate, adjust the value set
so that the output current
doesn't exceed the drive's
rated output current when
operating at low speeds.

0.00

to

2.50

1

Yes

A

A

A

No

No

341H

TrqCmp Gain
Mtr2

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2