User Parameter Tables

5-

19

b5-13

PID
Feedback Loss
Detection
Level

Sets the PID feedback loss
detection level as a
percentage (%) of maximum
frequency (E1-04).

0

to

100

0%

No

A

A

A

A

A

1B1H

Fb los Det
Lvl

b5-14

PID
Feedback
Loss
Detection
Time

Sets the PID feedback loss
detection delay time in terms
of seconds.

0.0

to

25.5

1.0 s

No

A

A

A

A

A

1B2H

Fb los Det
Time

b5-15

PID Sleep
Function
Start level

Sets the sleep function start
frequency.
Note: Enabled even when

PID control mode has
not been selected.

0.0

to

400.0

0.0Hz

No

A

A

A

A

A

1B3H

PID Sleep
Level

b5-16

PID Sleep
Delay Time

Sets the sleep function delay
time in terms of 0.1 seconds.

0.0

to

25.5

0.0 s

No

A

A

A

A

A

1B4H

PID Sleep
Time

b5-17

PID
Accel/decel
Time

Applies an accel/decel time to
the PID setpoint reference. The
Drive's standard softstarter
(C1-xx and S-curve) still
affects the output of the PID
algorithm.

0.0

to

25.5

0.0 s

No

A

A

A

A

A

1B5H

PID Acc/Dec
Time

b5-18

PID
Setpoint
Selection

Allows the b5-19 setting to be
the PID target setpoint value.
0: Disabled
1: Enabled

0 to 1

0

No

A

A

A

A

A

1DCH

PID
Setpoint Sel

b5-19

PID Setpoint

Sets the PID target value.
Use only when b5-18 = 1

0.0

to

100.0

0.0 %

No

A

A

A

A

A

1DDH

PID Setpoint

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2