Wiring the pg-x2, Wiring the pg-d2 – Yaskawa G7 Drive User Manual

Page 70

Advertising
background image

Installing and Wiring Option Cards

2-

39

„

Wiring the PG-D2

Wiring examples are provided in the following illustrations for the PG-D2.

•

Shielded twisted-pair wires must be used for signal lines.

•

Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.

•

The length of the pulse generator's wiring must not be more than 100 meters.

Fig 2.24 PG-D2 Wiring

„

Wiring the PG-X2

Wiring examples are provided in the following illustrations for the PG-X2.

•

Shielded twisted-pair wires must be used for signal lines.

•

Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.

•

The length of the pulse generator's wiring must not be more than 100 meters (328 ft).

•

The direction of rotation of the PG can be set in user parameter F1-05 (PG Rotation). The factory preset
if for motor forward rotation, A-phase advancement.

Fig 2.25 PG-X2 Wiring

Three-phase
200-240 Vac
(380-480 Vac)

Drive

Power supply +12 Vdc

Power supply 0 Vdc

Power supply +5 Vdc

Pulse input + (A/B phase)

Pulse input - (A/B phase)

Pulse monitor output

Three-phase
200-240 Vac
(380-480 Vac)

Drive

Power supply +12 Vdc

Power supply 0 Vdc
Power supply +5 Vdc
A-phase pulse input (+)
A-phase pulse input (-)
B-phase pulse input (+)
B-phase pulse input (-)

A-phase pulse monitor output

B-phase pulse monitor output

Z-phase pulse monitor output

R/L1

S/L2

U/T1

V/T2

W/T3

T/L3