Machine Protection

6-

51

‹

Motor Overload Protection

You can protect the motor from overload using the Drive's built-in electronic thermal overload relay.

„

Related Parameters

* 1. Factory settings will vary based on drive capacity (values given here are for 200-240V class, 0.4kW).
* 2. Setting range is 10% to 200% of the drive's rated output current (values given here are for 200-240V class, 0.4kW).

Multi-Function Outputs (H2-01 to H2-05)

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

E2-01

Motor Rated
Current

Sets the motor nameplate full load
current in amperes (A). This value
is automatically set during Auto-
Tuning.

0.32

to

6.40

*2

1.90 A

*1

No

Q

Q

Q

Q

Q

Motor Rated
FLA

E4-01

Motor 2 Rated
Current

Sets the motor 2 name plate full
load current in amperes (A). This
value is automatically set during
Auto-Tuning.

0.32

to

6.40

*2

1.90 A

*1

No

A

A

A

A

A

Motor Rated
FLA

L1-01

Motor Overload
Protection
Selection

Sets the motor thermal overload
protection (OL1) based on the
cooling capacity of the motor.

0: Disabled
1: Standard Fan Cooled

(< 10:1 motor)

2: Standard Blower Cooled

(

≤10:1 motor)

3: Vector Motor

(

≤1000:1 motor)In some

applications when the Drive
power supply is turned off, the
thermal value is reset, so even
if this parameter is set to 1,
protection may not be
effective.

When several motors are con-

nected to one Drive, set to 0 and
ensure that each motor is installed
with a protection device.

0 to 3

1

No

Q

Q

Q

Q

Q

MOL Fault
Select

L1-02

Motor Overload
Protection Time

Sets the motor thermal overload
protection (OL1) time. A larger
L1-02 time will increase the time
before an OL1 fault will occur.

0.1

to

5.0

1.0 min

No

A

A

A

A

A

MOL Time
Const

Setting

Value

Function

Control Methods

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

1F

Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection
level)

Yes

Yes

Yes

Yes

Yes