Protective and Diagnostic Functions

7-

7

OPR

Oper Dis-

connect

Digital Operator Connection Fault
The connection to the Digital Operator
was broken during operation for a
RUN command from the Digital
Operator.

-

Check the connection to the Digi-
tal Operator.

CE

Modbus

Com Err

MODBUS Communications Error
A normal reception was not possible
for 2 s or longer after control data was
received once.

-

Check the communications
devices and communications sig-
nals.

BUS

Option

Com Err

Option Communications Error
A communications error was detected
during a run command or while setting
a frequency reference from a Commu-
nications Option Card.

-

Check the communications
devices and communications sig-
nals.

E-15

SI-F/G

Com Err

SI-F/G Communications Error
Detected
A communications error was detected
when a run command or frequency
reference was set from an Option Card
and continuous operation was set for
the E-15 operation selection.

-

Check the communications sig-
nals.

E-10

SI-F/G

CPU down

SI-F/G Option Card CPU Failure
SI-F/G Option Card operation failed.

Digital Operator connection is faulty.

Disconnect and then reconnect the
Digital Operator.

Drive control circuit is faulty.

Replace the Drive.

CPF00

CPF

Digital Operator Communications
Error 1
Communications with the Digital
Operator were not established within 5
seconds after the power was turned
on.

The Digital Operator's connector isn't
connected properly.

Disconnect the Digital Operator
and then connect it again.

The Drive's control circuits are faulty. Replace the Drive.

CPU External RAM Fault

-

Try turning the power supply off
and on again.

The control circuits were destroyed.

Replace the Drive.

CPF01
CPF01

Digital Operator Communications
Error 2
After communications were estab-
lished, there was a communications
error with the Digital Operator for
more than 2 seconds.

The Digital Operator isn't connected
properly.

Disconnect the Digital Operator
and then connect it again.

The Drive's control circuits are faulty. Replace the Drive.

CPF02

BB Circuit

Err

Baseblock circuit error

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the Drive.

CPF03

EEPROM

Error

EEPROM error

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the Drive.

Table 7.1 Fault Displays and Processing (Continued)

Display

Meaning

Probable Causes

Corrective Actions