If there is mechanical oscillation, The machinery is making unusual sounds, If there is mechanical oscillation -25 – Yaskawa G7 Drive User Manual

Page 406

Advertising
background image

Troubleshooting

7-

25

‹

If the Ground Fault Interrupter Operates When the Drive is Run

The Drive performs internal switching, so there is a certain amount of leakage current. This may cause the
ground fault interrupter to operate and cut off the power supply. Change to a ground fault interrupter with a
high leakage detection level (i.e., a sensitivity current of 200 mA or greater per Unit, with an operating time of
0.1 s or more), or one that incorporates high frequency countermeasures (i.e., one designed for use with
Drives). It will also help to some extent to change the Drive's Carrier Frequency Selection (C6-02) to lower
the carrier frequency. In addition, remember that the leakage current increases as the cable is lengthened.

‹

If There is Mechanical Oscillation

Use the following information when there is mechanical oscillation.

„

The machinery is making unusual sounds.

The following causes are possible.

There may be resonance between the mechanical system's characteristic frequency and the
carrier frequency.

If the motor is running with no problems and the machinery is oscillating with a high-pitched whine, it may
indicate that this is occurring. To prevent this type of resonance, adjust the carrier frequency with parameters
C6-02 to C6-05.

There may be resonance between a machine's characteristic frequency and the output fre-
quency of the Drive.

To prevent this from occurring, either use the jump frequency functions in parameters d3-01 to d3-04 or install
rubber padding on the motor base to reduce oscillation.

„

Oscillation and hunting are occurring with open-loop vector control 1.

The gain adjustment may be insufficient. Reset the gain to a more effective level by adjusting parameters C4-
02 (torque compensation time parameter), C2-01 (S-curve Characteristic Time at Acceleration Start), and C3-
02 (Slip Compensation Primary Delay Time) in order. Lower the gain setting and raise the primary delay time
setting.

Vector control will not perform if autotuning has not been performed. Perform autotuning separately for the
motor, or set the motor parameters through calculations. Alternatively, change the control method selection
(A1-02) to V/f control (0 or 1).

„

Oscillation and hunting are occurring with V/f control.

The gain adjustment may be insufficient. Reset the gain to a more effective level by adjusting parameters C4-
02 (Torque Compensation Primary Delay Time Constant), n1-02 (Hunting Prevention Gain), and C3-02 (Slip
Compensation Primary Delay Time) in order. Lower the gain setting and raise the primary delay time setting.