6

-118

Table 11 V/f Pattern Default Settings for Drive Capacity 55~300kW for 240V Class (Continued)

Parameter

No.

Name

Unit

Factory Setting

E1-03

V/f Pattern Selection

8

9

A

B

C

D

E

F

E1-04

Max. Output
Frequency

Hz

50.0

50.0

60.0

60.0

90.0

120.0

180.0

60.0

E1-05

Max. Output Voltage

V

240.0

240.0

240.0

240.0

240.0

240.0

240.0

240.0

E1-06

Base
Frequency

Hz

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

E1-07

Mid. Output
Frequency A

V

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

E1-08

Mid. Output
Voltage A

V

17.2

23.0

17.2

23.0

13.8

13.8

13.8

13.8

E1-09

Min. Output
Frequency

Hz

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

E1-10

Mid. Output
Voltage

V

8.0

10.3

8.0

12.6

6.9

6.9

6.9

6.9

E1-11

Mid Output Fre-
quency B

Hz

0

0

0

0

0

0

0

0

E1-12

Mid Output Voltage
B

V

0

0

0

0

0

0

0

0

E1-13

Base Voltage

V

0

0

0

0

0

0

0

0

For 480V class units, the value is twice that of 240V class units.