Related parameters, Using the dc injection brake – Yaskawa G7 Drive User Manual

Page 230

Advertising
background image

Stopping Methods

6-

13

‹

Using the DC Injection Brake

Set parameter b2-03 to apply the DC injection brake voltage to the motor while it is coasting to a stop, to stop
the motor and then restart it.

Set b2-03 to 0 to disable the DC injection brake at start.

Set the DC injection brake current using b2-02. DC injection braking is used at startup for flux vector control
with the current set in E2-03 (Motor no-load current).

„

Related Parameters

„

Inputting the DC Injection Brake Command from Control Circuit Terminals

If you set a multi-function contact input terminal (H1-††) to 60 (DC injection brake command), you can
apply the DC injection brake to the motor by turning ON the terminal for which the DC injection brake com-
mand has been set when the Drive is being stopped. DC injection braking is used at startup for flux vector con-
trol.

The time chart for the DC injection brake is shown below.

Fig 6.16 DC Injection Brake Time Chart

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b2-02

DC Injection
Braking
Current

Sets the DC injection braking
current as a percentage of the
Drive rated current.
Note: The DC excitation current
is determined by the setting in E2-
03 when operating in flux loop
vector control mode.

0

to

100

50%

No

A

A

A

No

No

DCInj Current

b2-03

DC Injection
Braking Time/
DC Excitation
Time at Start

Sets the time of DC injection
braking at start in units of 0.01
seconds.

0.00

to

10.00

0.00sec

No

A

A

A

A

A

DCInj
Time@Start

DC injection brake

(DC injection braking at

startup is used for flux

vector control.)

E1-09

b2-01

DC injection brake command

FRUN

Output frequency

DC injection brake

(DC injection braking at

startup is used for flux

vector control.)

If you input the DC injection brake command from an external terminal, or if the run command

and jog command are input, the DC injection brake will be disabled, and operation will

resume.

Advertising