Time chart, Application precautions – Yaskawa G7 Drive User Manual

Page 355

Advertising
background image

6

-138

„

Time Chart

A time chart for the zero servo function is given in Fig 6.74 Time Chart for Zero Servo.

Fig 6.74 Time Chart for Zero Servo

„

Application Precautions

•

Be sure to leave the run command input ON. If the run command is turned OFF, the output will be inter-
rupted and the zero-servo function will become ineffective.

•

The holding force of the zero-servo is adjusted in b9-01. The holding force will increase if the value of the
setting is increased, but oscillation and hunting will occur if the setting is too large. Adjust b9-01 after
adjusting the speed control gain.

•

The zero-servo detection width is set as the allowable position offset from the zero-servo start position. Set
4 times the number of pulses from the PG.

•

The Zero Servo End signal will go OFF when the zero servo command is turned OFF.

IMPORTANT

Do not lock the servo for extended periods of time at 100% when using the zero servo function. Drive errors
may result. Extended periods of servo lock can be achieved by ensuring that the current during the servolock
is 50% or less or by increasing the Drive capacity.

Run command

ON

OFF

Zero servo command

Frequency (speed) reference

Excitation level

b2-01

Motor speed

Zero Servo End signal

Zero-servo status

ON

OFF