Yaskawa G7 Drive User Manual

Page 116

Advertising
background image

Digital Operator Display Functions and Levels

5-

5

C6-02

Carrier
Frequency
Selection

Selects the number of pulses per
second of the output voltage
waveform. Setting range determined
by C6-01 setting.
0: Low noise
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
OF: Program (Determined by the

settings of C6-03 thru C6-05)

0 to F

6

*2

No

Q

Q

Q

Q

-

*12

224H

Carrier
Freq Sel

C6-11

Carrier
Frequency
for
Open-loop
Vector
Control 2

Selects the carrier frequency during
Vector Control 2 wo/PG.
1: 2kHz (3-phase modulation)
2: 4kHz (3-phase modulation)
3: 6kHz (3-phase modulation)
4: 8kHz (3-phase modulation)

1 to 4

4

*2

No

-

*12

-

*12

-

*12

-

*12

Q

22DH

Carrier
Freq Sel

d1-01

Frequency
Reference 1 Setting units are affected by o1-03.

0

to

400.00

*9

0.00Hz

Yes

A

A

A

A

A

280H

Reference 1

d1-02

Frequency
Reference 2

Frequency reference when
multi-function input "Multi-step speed
reference 1" is ON. Setting units are
affected by o1-03.

0.00Hz

Yes

A

A

A

A

A

281H

Reference 2

d1-03

Frequency
Reference 3

Frequency reference when
multi-function input "Multi-step speed
reference 2" is ON. Setting units are
affected by o1-03.

0.00Hz

Yes

A

A

A

A

A

282H

Reference 3

d1-04

Frequency
Reference 4

Frequency reference when
multi-function input "Multi-step speed
reference 1, 2" is ON. Setting units are
affected by o1-03.

0.00Hz

Yes

A

A

A

A

A

283H

Reference 4

d1-17

Jog
Frequency
Reference

Frequency reference when: "Jog
frequency reference" is selected via
multi-function input terminals. "Jog
frequency reference" has priority over
"multi-step speed reference 1 to 4".
Parameter d1-17 is also the reference
for the JOG key on the Digital Opera-
tor, and the multi-function inputs
"forward jog" and "reverse jog".
Setting units are affected by o1-03.

6.00Hz

Yes

Q

Q

Q

Q

Q

292H

Jog
Reference

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS
Register

Display

V/f

V/f

with

PG

Open

-loop

Vector

1

Flux

Vector

Open

Loop

Vector

2