Yaskawa G7 Drive User Manual

Page 242

Advertising
background image

Adjusting Frequency References

6-

25

„

Adjusting Analog Frequency Reference Using Parameters

The frequency reference is input from the control circuit terminals using analog voltage and current.
If using frequency reference terminal A1 as an input terminal, perform adjustments using parameters H3-02
and H3-03. If using multi-function analog input terminal A2 as a frequency reference terminal, perform
adjustments using H3-10 and H3-11.
Adjustment can be made using H3-06 and H3-07 when multi-function analog input terminal A3 is used as a
frequency reference terminal.

Fig 6.24 Terminals A1 and A2 Inputs

H3-08

Terminal A2
Signal Level
Selection

Selects the signal level of

terminal A2.

0: 0 to 10Vdc (switch S1-2 must

be in the OFF position).

1: -10 to +10Vdc (switch S1-2

must be in the OFF position).

2: 4 to 20mA (switch S1-2 must

be in the ON position)

Note: Switch between current or
voltage inputs by using (S1-2)
switch on the terminal board.

0 to 2

2

No

A

A

A

A

A

Term A2 Signal

H3-09

Terminal A2
Function
Selection

Selects the function of terminal
A2.
Same choices as Terminal A3
Function Selection (H3-05).

0 to 1F

0

No

A

A

A

A

A

Terminal A2
Sel

H3-10

Terminal A2
Gain Setting

Sets the output level when 10V is
input.

0.0

to

1000.0

100.0%

Yes

A

A

A

A

A

Terminal A2
Gain

H3-11

Terminal A2
Bias Setting

Sets the output level when 0V is
input.

-100.0

to

100.0

0.0%

Yes

A

A

A

A

A

Terminal A2
Bias

H3-12

Analog Input
Filter Time
Constant

This parameter adjusts the filter
on all 3 analog inputs. Increase to
add stability, decrease to improve
response.

0.00

to

2.00

0.03sec

No

A

A

A

A

A

Filter Avg Time

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

Frequency reference

Terminal A1, A3 input

Terminal A1 (A3)
input voltage

Frequency reference

Terminal A2 input

Terminal A2 input
voltage (current)

(H3-06)

(H3-07)

Advertising