Multi-function analog outputs: h4 – Yaskawa G7 Drive User Manual

Page 169

Advertising
background image

5

-58

„

Multi-function Analog Outputs: H4

User parameters for multi-function analog outputs are shown in the following table.

* In order to adjust the meter, 100% of the appropriate output is multiplied for the gain setting, the bias amount is added and then output.

See H4-02 when stopped in Quick, Advanced, or Verify mode. If 03 appears on the setting screen, then terminal FM is used.
See H4-04 when stopped in Quick, Advanced, or Verify mode. If 06 appears on the setting screen, then terminal AM is used.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

H4-01

Terminal
FM
Monitor
Selection

Selects the monitor output
(U1-xx) function for terminals
FM and FC. Refer to "U1-xx"
monitors for available settings.
Unavailable settings:
4, 10, 11, 12, 13, 14, 25, 28, 29,
30, 31, 34, 35, 39, 40, 41, 42,
47, 49, 50

1 to 48

2

No

A

A

A

A

A

41DH

Terminal
FM Sel

H4-02

Terminal
FM Gain
Setting

Sets terminal FM output level
when selected monitor is at
100%.*

0.00

to

2.50

1.00

Yes

Q

Q

Q

Q

Q

41EH

Terminal
FM Gain

H4-03

Terminal
FM Bias
Setting

Sets terminal FM output level
when selected monitor is at
0%.*

-10.0

to

10.0

0.0%

Yes

A

A

A

A

A

41FH

Terminal
FM Bias

H4-04

Terminal
AM
Monitor
Selection

Selects which monitor will be
the output on terminals AM and
FC. Same function choices as
H4-01.

1 to 48

3

No

A

A

A

A

A

420H

Terminal
AM Sel

H4-05

Terminal
AM Gain
Setting

Sets terminal AM output
voltage (in percent of 10Vdc)
when selected monitor is at
100% output.*

0.00

to

2.50

0.50

Yes

Q

Q

Q

Q

Q

421H

Terminal
AM Gain

H4-06

Terminal
AM Bias
Setting

Sets terminal AM output
voltage (in percent of 10Vdc)
when selected monitor is at 0%
output.*

-10.0

to

10.0

0.0%

Yes

A

A

A

A

A

422H

Terminal
AM Bias

H4-07

Terminal
FM Signal
Level
Selection

Selects the signal level of
terminal FM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*
*Set the analog output jumper

CN15 in the proper position.

0 to 2

0

No

A

A

A

A

A

423H

AO Level
Select1

H4-08

Terminal
AM Signal
Level
Selection

Selects the signal level of
terminal AM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*
*Set the analog output jumper

CN15 in the proper position.

0 to 2

0

No

A

A

A

A

A

424H

AO Level
Select 2

Advertising