Yaskawa G7 Drive User Manual

Page 211

Advertising
background image

5

-100

„

208-240Vac Drives of 55 to 110 kW and 380-480Vac Drives of 55 to 300 kW

Table 5.5 V/F Pattern for Drive Capacity G7U2055 and higher for 208-240V Class

Parameter

No.

Name

Unit

Factory Setting

E1-03

V/F Pattern
Selection

0

1

2

3

4

5

6

7

E1-04

Max. Output
Frequency

Hz

50.0

60.0

60.0

72.0

50.0

50.0

60.0

60.0

E1-05

Max. Output
Voltage

V

230.0

230.0

230.0

230.0

230.0

230.0

230.0

230.0

E1-06

Max. Voltage
Frequency

Hz

50.0

60.0

50.0

60.0

50.0

50.0

60.0

60.0

E1-07

Mid. Output
Frequency

V

2.5

3.0

3.0

3.0

25.0

25.0 30.0

30.0

E1-08

Mid. Output
Voltage

V

13.8

13.8

13.8

13.8

40.2

57.5

40.2

57.5

E1-09

Min. Output
Frequency

Hz

1.3

1.5

1.5

1.5

1.3

1.3

1.5

1.5

E1-10

Min. Output
Voltage

V

6.9

6.9

6.9

6.9

5.7

6.9

5.7

6.9

1.

The setting shown are for 208-240Vac Drives. The values will double for 380-480Vac Drives.

.

2. These default values are for V/F or V/F with PG control methods (A1-02 = 0 or 1)

Table 5.5 V/F Pattern for Drive Capacity G7U2055 and higher for 208-240V Class (continued)

Parameter

No.

Name

Unit

Factory Setting

E1-03

V/F Pattern
Selection

8

9

A

B

C

D

E

F & FF

E1-04

Max. Output
Frequency

Hz

50.0

50.0

60.0

60.0

90.0

120.0

180.0

60.0

E1-05

Max. Output
Voltage

V

230.0

230.0

230.0

230.0

230.0

230.0

230.0

230.0

E1-06

Base Frequency

Hz

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

E1-07

Mid. Output
Frequency

V

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

E1-08

Mid. Output
Voltage

V

17.2

23.0

17.2

23.0

13.8

13.8

13.8

13.8

E1-09

Min. Output
Frequency

Hz

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

E1-10

Min. Output
Voltage

V

8.0

10.3

8.0

12.6

6.9

6.9

6.9

6.9

1.

The setting shown are for 208-240Vac Drives. The values will double for 380-480Vac Drives.

2. These default values are for V/F or V/F with PG control methods (A1-02 = 0 or 1)