Manual motor parameter setting methods, Motor rated voltage setting, Motor rated slip setting – Yaskawa G7 Drive User Manual

Page 327: Motor no-load current setting, Number of motor poles setting, Motor line-to-line resistance setting, Motor leak inductance setting, Motor iron loss for torque compensation setting, Motor mechanical loss

Advertising
background image

6

-110

„

Manual Motor Parameter Setting Methods

The motor parameter settings methods are given below. Make (enter) settings referring to the motor test
report.

Motor Rated Voltage Setting

Set E2-01 to the rated current on the motor nameplate.

Motor Rated Slip Setting

Set E2-02 to the motor rated slip calculated from the number of rated rotations on the motor nameplate.

Amount of motor rated slip = Motor rated frequency (Hz) - No. of rated rotations (min

−1

) x No. of motor

poles/120.

Motor No-Load Current Setting

Set E2-03 to the motor no-load current using the rated voltage and rated frequency. The motor no-load current
is not normally written on the motor nameplate. Consult the motor manufacturer.

Factory setting is the no-load current value for a standard Yaskawa 4-pole motor.

Number of Motor Poles Setting

E2-04 is displayed only when V/f control method with PG is selected. Set the number of motor poles (number
of poles) as written on the motor nameplate.

Motor Line-to-Line Resistance Setting

E2-05 is set automatically when performing motor

line-to-line resistance autotuning. When you cannot perform tun-

ing, consult the motor manufacturer for the line-to-line resistance value. Calculate the resistance from the line-to-line resis-
tance value in the motor test report using the following formula, and then make the setting accordingly.

E-type isolation: [Line-to line resistance (

Ω) at 75°C of test report] × 0.92 (Ω)

B-type isolation: [Line-to line resistance (

Ω) at 75°C of test report] × 0.92 (Ω)

F-type isolation: [Line-to line resistance (

Ω) at 115°C of test report] × 0.87 (Ω)

Motor Leak Inductance Setting

Set the amount of voltage drop due to motor leak inductance in E2-06 using the percentage over the motor
rated voltage. Make this setting when the high-speed motor inductance is small. If the inductance is not writ-
ten on the motor nameplate, consult the motor manufacturer.

Motor Iron Saturation Coefficients 1 and 2 Settings

E2-07 and E2-08 are set automatically using autotuning.

Motor Iron Loss for Torque Compensation Setting

E2-10 is displayed only when in V/f control method. To increase the torque compensation accuracy when in
V/f control method, set the motor iron loss in Watts.

Motor Mechanical Loss

When using flux vector control, adjust mechanical loss in the following cases. (There is normally no reason to
make this adjustment.) The mechanical loss setting is used to compensate the torque.

There is excessive torque loss from the motor bearings.

There is excessive torque loss from a fan, pump, etc.

Advertising