Individual Functions

6-

107

‹

Energy-saving

To perform energy saving, set b8-01 (Energy Saving Mode Selection) to 1. Energy-saving control can be per-
formed using both V/f control and open-loop vector control. The parameters to be adjusted are different for
each. In V/f control, adjust b8-04 to b8-06, and in vector control, adjust b8-02 and b8-03.

„

Related Parameters

* 1. Set to 1.0 in Vector Control Mode with PG.
* 2. Initial settings vary based on drive capacity and control mode.
* 3. Caution: Initial settings will vary based on motor capacity
* 4. Initial/Default settings vary based on drive capacity. Values shown here are for 200-240V class 0.4kW drives.

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b8-01

Energy Saving
Control
Selection

Energy Savings function enable/
disable selection.
0: Disabled
1: Enabled

0 or 1

0

No

A

A

A

A

A

Energy Save
Sel

b8-02

Energy Saving
Gain

Sets energy savings control gain
when in vector control mode.

0.0

to

10.0

0.7

*1

Yes

No

No

A

A

A

Energy Save
Gain

b8-03

Energy Saving
Control Filter
Time Constant

Sets energy saving control filter
time constant when in vector
control mode.

0.00

to

10.0

0.50sec

*2

Yes

No

No

A

A

A

Energy Save
F.T

b8-04

Energy Saving
Coefficient
Value

Used to fine-tune the energy
savings function when in V/f
Control Mode.

0.0

to

655.00

*3
*4

No

A

A

No

No

No

Energy Save
COEF

b8-05

Power
Detection Filter
Time

Used to fine-tune the energy
savings function when in V/f
Control Mode.

0

to

2000

20ms

No

A

A

No

No

No

kW Filter Time

b8-06

Search
Operation
Voltage Limit

Used to fine-tune the energy
savings function when in V/f
Control Mode.

0 to 100

0%

No

A

A

No

No

No

Search V Limit

E2-02

Motor Rated
Slip

Sets the motor rated slip in hertz
(Hz). This value is automatically
set during rotational
Auto-Tuning.

0.00

to

20.00

2.90Hz

*4

No

A

A

A

A

A

Motor Rated
Slip

E2-11

Motor Rated
Output

Sets the motor rated power in
kilowatts (kW). This value is
automatically set during
Auto-Tuning. 1HP = 0.746kW

0.00

to

650.00

0.40kW

*3

No

Q

Q

Q

Q

Q

Mtr Rated
Power