Fault history: u3 – Yaskawa G7 Drive User Manual

Page 205

Advertising
background image

5

-94

„

Fault History: U3

User parameters for the error log are shown in the following table.

Parameter

Number

Name

Description

Output Signal Level

During Multi-Function

Analog Output

Min.

Unit

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

U3-01

Most Recent
Fault

Shows the most recent fault.

No output possible.

-

A

A

A

A

A

90H

Last Fault

U3-02

2nd Most
Recent Fault

Shows the second most
recent fault.

-

A

A

A

A

A

91H

Fault
Message 2

U3-03

3rd Most
Recent Fault

Shows the third most recent
fault.

-

A

A

A

A

A

92H

Fault
Message 3

U3-04

4th Most
Recent Fault

Shows the fourth most
recent fault.

-

A

A

A

A

A

93H

Fault
Message 4

U3-05

Cumulative
Operation
Time at Most
Recent Fault

Gives the cumulative
operation time at the most
recent fault.

1

hr

A

A

A

A

A

94H

Elapsed Time 1

U3-06

Cumulative
Operation
Time at 2nd
Most Recent
Fault

Gives the cumulative
operation time at the second
most recent fault.

1

hr

A

A

A

A

A

95H

Elapsed Time 2

U3-07

Cumulative
Operation
Time at 3rd
Most Recent
Fault

Gives the cumulative
operation time at the third
most recent fault.

1

hr

A

A

A

A

A

96H

Elapsed Time 3

U3-08

Cumulative
Operation
Time at 4th
Most Recent
Fault

Gives the cumulative
operation time at the fourth
most recent fault.

1

hr

A

A

A

A

A

97H

Elapsed Time 4

U3-09

5th Most
Recent Fault

Shows the fifth most recent
fault.

-

A

A

A

A

A

804H

Fault
Message 5

U3-10

6th Most
Recent Fault

Shows the sixth most recent
fault.

-

A

A

A

A

A

805H

Fault Message 6

Advertising