5-

21

„

Energy Saving: b8

User parameters for energy-saving control functions are shown in the following table.

* 1. The factory setting is 1.0 when using V/f control with PG.
* 2. Initial settings vary based on drive capacity and control mode.
* 3. Caution: Initial settings will vary based on motor capacity.

„

Zero Servo: b9

User parameters for dwell functions are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b8-01

Energy Saving
Control
Selection

Energy Savings function
enable/disable selection.
0: Disabled
1: Enabled

0 or 1

0

No

A

A

A

A

A

1CCH

Energy Save
Sel

b8-02

Energy
Saving Gain

Sets energy savings control
gain when in vector control
mode.

0.0

to

10.0

0.7

*1

Yes

No

No

A

A

A

1CDH

Energy Save
Gain

b8-03

Energy Saving
Control
Filter Time
Constant

Sets energy saving control
filter time constant when in
vector control mode.

0.00

to

10.0

0.50 s

*2

Yes

No

No

A

A

A

1CEH

Energy
Saving F.T

b8-04

Energy Saving
Coefficient
Value

Used to fine-tune the energy
savings function when in V/f
Control Mode.

0.0

to

655.00

*3

No

A

A

No

No

No

1CFH

Energy Save
COEF

b8-05

Power Detection
Filter Time

Used to fine-tune the energy
savings function when in V/f
Control Mode.

0

to

2000

20ms

No

A

A

No

No

No

1D0H

kW Filter Time

b8-06

Search
Operation
Voltage Limit

Used to fine-tune the energy
savings function when in V/f
Control Mode.

0

to

100

0%

No

A

A

No

No

No

1D1H

Search V Limit

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b9-01

Zero-servo
Gain

Sets the position loop gain for
Zero Servo command. This
function is effective when
multi-function input
"zero- servo command" is set.

0

to

100

5

No

No

No

No

A

No

1DAH

Zero Servo
Gain

b9-02

Zero-servo
Completion
Width

Sets number of pulses used
for the multi-function output
of "zero servo completion".

0

to

16383

10

No

No

No

No

A

No

1DBH

Zero Servo
Count

Advertising