Continuing Operation

6-

63

Speed Search after Short Baseblock (during Power Loss Recovery, etc.)

Loss Time Shorter Than the Minimum Baseblock Time (L2-03)

Fig 6.43 Speed Search after Baseblock (When Estimated Speed: Loss Time Is Set in L2-03)

Loss Time Longer Than the Minimum Baseblock Time (L2-03)

Fig 6.44 Speed Search After Baseblock (Estimated Speed: Loss Time > L2-03)

„

Current Detection Speed Search

The time charts for current detection speed search is shown below.

Speed Search at Startup

The time chart when speed search at startup or external speed search command is selected is shown below.

AC power supply

Output frequency

Output current

OFF

ON

Start using
speed detected

Set frequency
reference

Minimum baseblock time (L2-03) x 0.75*1

10 ms

*1 Baseblock time may be reduced by the output frequency
immediately before the baseblock.
*2 After AC power supply recovery, motor waits for the
minimum Speed Search Wait Time (b3-05).

*2

AC power supply

Output frequency

Output current

OFF

ON

Start using speed detected

Set frequency
reference

Minimum baseblock time
(L2-03)

10 ms

Speed Search Wait Time
(b3-05)