-12

4/0

100

M10

100 - 10

M12

100 - 12

M16

100 - 16

250 / 300MCM

125 / 150

M10

150 - 10

M12

150 - 12

M16

150 - 16

400MCM

200

M12

200 - 12

650MCM

325

M12 x 2

325 - 12

M16

325 - 16

*

Wire sizes are based on 75 degrees Celsius copper wire.

** Equivalent connector can be used.

IMPORTANT

Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
voltage drop is calculated as follows:

Line voltage drop (V) =

x wire resistance (W/km) x wire length (m) x current (A) x 10

-3

Wire Size *

Terminal Screw

Ring Tongue (R-Type) Closed-Loop Connectors (Lugs)

JST Corporation Part Numbers **

3