Standard Drive Specifications

9-

3

„

380-480 V Class

* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting the actual motor and Drive, be sure that the Drive's rated

current is applicable for the motor's rated current.

* 2. A 3-wire transformer (optional) is required on the power supply for 12-phase rectification.

Table 9.2 380-480 V Class Drives

Model Number CIMR-G7U †

40P4

40P7

41P5

42P2

43P7

44P0

45P5

47P5

4011

4015

4018

Max. applicable motor output
(kW)

*1

0.4

0.75

1.5

2.2

3.7

4.0

5.5

7.5

11

15

18.5

Rated output capacity
(kVA)

1.4

2.6

3.7

4.7

6.9

8.4

11

16

21

26

32

Rated output current (A)

1.8

3.4

4.8

6.2

9

11

15

21

27

34

42

Max. output voltage (V)

3-phase; 380, 400, 415, 440, 460, or 480 Vac (Proportional to input voltage.)

Max. output frequency
(Hz)

Frequencies supported up to 400 Hz using parameter setting

Rated voltage (V)
Rated frequency (Hz)

3-phase, 380, 400, 415, 440, 460 or 480 Vac, 50/60 Hz

Allowable voltage
fluctuation

+ 10%, - 15%

Allowable frequency
fluctuation

±5%

Measures for
power supply
harmonics

DC link
choke

Optional

Built in

12-phase
rectification

Not possible

Possible

*2

Model Number CIMR-G7U †

4022

4030

4037

4045

4055

4075

4090

4110

4132

4160

4185

4220

4300

Max. applicable motor output
(kW)

*1

22

30

37

45

55

75

90

110

132

160

185

220

300

Rated output capacity
(kVA)

40

50

61

74

98

130

150

180

210

230

280

340

460

Rated output current (A)

52

65

80

97

128

165

195

240

270

302

370

450

605

Max. output voltage (V)

3-phase, 380, 400, 415, 440, 460, or 480 Vac (Proportional to input voltage.)

Max. output frequency
(Hz)

Frequencies supported up to 400 Hz using parameter setting

Max. voltage (V)
Rated frequency (Hz)

3-phase, 380, 400, 415, 440, 460, or 480 Vac, 50/60 Hz

Allowable voltage
fluctuation

+ 10%, - 15%

Allowable frequency
fluctuation

±5%

Measures for
power supply
harmonics

DC link
choke

Built in

12-phase
rectification

Possible

*2

Out

put

r

at

ings

Po

wer

s

uppl

y characteris

tics

Out

put

r

at

ings

Power s

uppl

y c

ha

ract

er

is

ti

cs

Advertising