Table 4.2 Parameters that Are Set as Required

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

b1-03

Stopping method
selection

Select stopping method when stop command is
sent.

0: Deceleration to stop
1: Coast to stop
2: DC braking stop
3: Coast to stop with timer

0 to 3

0

C6-02

Carrier fre-
quency selection

The carrier frequency is set low if the motor cable
is 50 m or longer or to reduce radio noise or leak-
age current.

1 to F

Depends

on capac-

ity, volt-
age, and

control

mode.

C6-11

Carrier fre-
quency selection
for open-loop
vector control 2

1 to 4

Depends

on kVA

setting.

d1-01 to

d1-04 and

d1-17

Frequency refer-
ences 1 to 4 and
jog frequency ref-
erence

Set the required speed references for multi-step
speed operation or jogging.

0.00 to

400.00 Hz

d1-01 to

d1-04:

0.00Hz

d1-17:

6.00Hz

H4-02

and H4-

05

FM and AM ter-
minal output gain

Adjust when an instrument is connected to the FM
or AM terminal.

0.0 to 1000.0

H4-02:

100%

H4-05:

50%

L3-04

Stall prevention
selection during
deceleration

If using the dynamic brake option (braking resis-
tor, Braking Resistor Units, and Braking Units), be
sure to set parameter L3-04 to 0 (disabled) or 3
(enabled with braking resistor).

0 to 3

1