Motor overload: l1, Protection function parameters: l – Yaskawa G7 Drive User Manual

Page 172

Advertising
background image

User Parameter Tables

5-

61

‹

Protection Function Parameters: L

The following settings are made with the protection function parameters (L parameters): Motor selection
function, power loss ridethrough function, stall prevention function, frequency detection, torque limits, and
hardware protection.

„

Motor Overload: L1

User parameters for motor overloads are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L1-01

Motor
Overload
Protection
Selection

Sets the motor thermal
overload protection (OL1)
based on the cooling capacity
of the motor.
0: Disabled
1: Standard Fan Cooled
(< 10:1 motor)
2: Standard Blower Cooled

(≥10:1 motor)
3: Vector Motor
(

≤1000:1 motor)

0 to 3

1

No

Q

Q

Q

Q

Q

480H

MOL Fault
Select

L1-02

Motor
Overload
Protection
Time

Sets the motor thermal
overload protection (OL1)
time. A larger L1-02 time will
increase the time before an
OL1 fault will occur.

0.1

to

5.0

1.0 min

No

A

A

A

A

A

481H

MOL Time
Const

L1-03

Motor
Overheat
Alarm
Operation
Selection

Sets operation selection when

the motor temperature analog
input (H3-09 = E) exceeds the
OH3 alarm level (1.17V)

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

No

A

A

A

A

A

482H

Mtr OH
Alarm Sel

L1-04

Motor
Overheat
Fault
Operation
Selection

Sets stopping method when

the motor temperature analog
input

(H3-09 = E) exceeds the OH4

fault level (2.34V).

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop

0 to 2

1

No

A

A

A

A

A

483H

Mtr OH
Fault Sel

L1-05

Motor
Temperatur
e Input
Filter Time

This parameter adjusts the filter
on the motor temperature
analog input (H3-09 = E).
Increase to add stability,
decrease to improve response.

0.00

to

10.00

0.20sec

No

A

A

A

A

A

484H

Mtr Temp
Filter

Advertising