Individual Functions

6-

121

d5-05

Speed Limit
Bias

Sets the speed limit bias as a
percentage of the maximum
output frequency (E1-04). Bias is
given to the specified speed limit.
It can be used to adjust the margin
for the speed limit.

0 to 120

10%

No

No

No

No

A

A

Speed Lmt Bias

d5-06

Speed/Torque
Control
Switchover
Timer

Sets the delay time from inputting
the multi-function input "speed/
torque control change" (from On
to OFF or OFF to ON) until the
control is actually changed. This
function is enabled when the
multi-function input "speed/
torque control change"
(H1-xx= 71) is set. While in the
speed/torque control switching
timer, the analog inputs hold the
value present when the "speed/
torque control change" is
received.

0

to

1000

0ms

No

No

No

No

A

A

Ref Hold Time

H3-04

Terminal A3
Signal Level
Selection

Sets the signal level of terminal

A3.

0: 0 to 10Vdc
1: -10 to +10Vdc

0 to 1

0

No

A

A

A

A

A

Term A3 Signal

H3-05

Terminal A3
Function
Selection

[Refer to table "H3-05, H3-09
Settings" for multi-function
selections]

0 to 1F

2

No

A

A

A

A

A

Terminal A3
Sel

H3-06

Terminal A3
Gain Setting

Sets the output level when 10V is
input.

0.0

to

1000.0

100.0%

Yes

A

A

A

A

A

Terminal A3
Gain

H3-07

Terminal A3
Bias Setting

Sets the frequency reference when
0V is input.

-100.0

to

+100.0

0.0%

Yes

A

A

A

A

A

Terminal A3
Bias

H3-08

Terminal A2
Signal Level
Selection

Selects the signal level of terminal
A2.
0: 0 to 10Vdc (switch S1-2 must
be in the OFF position).
1: -10 to +10Vdc (switch S1-2
must be in the OFF position).
2: 4 to 20mA (switch S1-2 must
be in the ON position)
Note: Switch between current or
voltage inputs by using (S1-2)
switch on the terminal board.

0 to 2

2

No

A

A

A

A

A

Term A2 Signal

H3-09

Terminal A2
Function
Selection

Selects the function of terminal
A2.
Same choices as Terminal A3
Function Selection (H3-05).

0 to 1F

0

No

A

A

A

A

A

Terminal A2
Sel

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2