Trial Operation Procedures

4-

7

‹

Settings for the Control Methods

Autotuning methods depend on the control method set for the Drive. Make the settings required by the control
method.

„

Overview of Settings

Make the required settings in quick programming mode and autotuning mode according to the following flow-
chart.

Note If the motor cable changes to 50 m or longer for the actual installation, perform stationary autotuning for the line-to-line resistance only on-site.
* 1. Use rotational autotuning to increase autotuning accuracy whenever it is okay for the motor to be operated. Always perform rotational autotuning when

using open-loop vector control 2.

* 2. If there is a reduction gear between the motor and PG, set the reduction ratio in F1-12 and F1-13.
* 3. The default setting of the Drive is for open-loop vector control 1 (A1-02 = 2).
* 4. If the maximum output frequency and base frequency are different, set the maximum output frequency (E1-04) after autotuning.

Fig 4.3 Settings According to the Control Method

START

YES
V/f

V/f control?

(A1-02 = 0 or 1)

PG?

Motor cable over

50 m or heavy load possibly

causing motor to stall

or overload?

NO

(Default: A1-02 = 0)

YES

(A1-02 = 1)

NO
Vector (A1-02 = 2, 3, or 4)*3

Set E1-03.
V/f default: 200 V/60 Hz(400 V/60 Hz)

Set E1-03, E2-04, and F1-01.
V/f default: 200 V/60 Hz(400 V/60 Hz)

NO

YES

YES

NO

END

*2

Control mode selection

OK to operate

motor during autotuning?*1

Rotational autotuning*4

Stationary autotuning*4

Stationary autotuning for
line-to-line resistance only