Digital Operator Functions

6-

143

‹

Copying Parameters

The Digital Operator can perform the following three functions using the built-in EEPROM (non-volatile
memory).

•

Store Drive parameter set values in the Digital Operator (READ)

•

Write parameter set values stored in the Digital Operator to the Drive (COPY)

•

Compare parameter set values stored in the Digital Operator with Drive parameters (VERIFY)

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

o3-01

Copy Function
Selection

This parameter controls the

copying of parameters to and
from the Digital Operator.

0: COPY SELECT (no function)
1: INV --> OP READ - All

parameters are copied from the
Drive to the Digital Operator.

2: OP --> INV WRITE - All

parameters are copied from the
Digital Operator to the Drive.

3: OP<-->INV VERIFY -

Parameter settings in the Drive
are compared to those in the
Digital Operator.

Note: When using the copy

function, the Drive model
number (o2-04), software
number (U1-14), and control
method (A1-02) must match or
an error will occur.

0 to 3

0

No

A

A

A

A

A

Copy Function
Sel

o3-02

Copy Allowed
Selection

Enables and disables the Digital
Operator copy functions.
0: Disabled - No Digital Operator

copy functions are allowed.

1: Enabled - Copying allowed.

0 to 1

0

No

A

A

A

A

A

Read Allowable