Drive mode indicators, Remote sequence (seq) indicator, Remote reference (ref) indicator – Yaskawa G7 Drive User Manual

Page 77

Advertising
background image

3

-4

Drive Mode Indicators

The definition of the Drive mode indicators are shown in Table 3.2.

‹

REMOTE Sequence (SEQ) Indicator

The status of the “REMOTE” Sequence (SEQ) indicator is shown in Table 3.3. This indicator is always “Off” when the Drive is

in the “LOCAL” mode. When the Drive is in the “REMOTE” mode, the SEQ indicator status is dependent on the setting of

parameter b1-02 (Run Command Selection). See Table 3.3.

‹

REMOTE Reference (REF) Indicator

The status of the “REMOTE” Reference (REF) indicator is shown in Table 3.4. This indicator is always “Off” when the Drive is

in the “LOCAL” mode. When the Drive is in the “REMOTE” mode, the REF indicator status is dependent on the setting of

parameter b1-01 (Frequency Reference Selection). See Table 3.4.

Table 3.2 Drive Mode Indicators

Indicator

Definition

FWD

Lit when a forward run command is input.

REV

Lit when a reverse run command is input.

REMOTE SEQ

See Table 3.3.

REMOTE REF

See Table 3.4.

ALARM

Lit when a fault has occurred. Flashes when an Alarm has occurred.

Table 3.3 REMOTE Sequence (SEQ) Indicator

Indicator Status

Condition

On

Parameter b1-02 (Run Command Selection) is set to terminal strip, communications, or an option
board as indicated below:
b1-02 =1 (Terminals)
=2 (Communications)
=3 (Option PCB)

Off

Parameter b1-02 (Run Command Selection) is set to Digital Operator as indicated below:
b1-02=0 (Operator)

Table 3.4 REMOTE Reference (REF) Indicator

Indicator Status

Condition

On

Parameter b1-01 (Frequency Reference Selection) is set to terminal strip, communications, option
board, or pulse train as indicated below:
b1-01 =1 (Terminals)
=2 (Communications)
=3 (Option PCB)
=4 (Pulse Train)

Off

Parameter b1-01 (Frequency Reference Selection) is set to digital
operator as indicated below:
b1-01=0 (Operator)

Advertising