Yaskawa G7 Drive User Manual

Page 117

Advertising
background image

5

-6

E1-01

Input
Voltage
Setting

Set to the nominal voltage of the
incoming line. Sets the maximum and
base voltage used by preset V/F
patterns (E1-03 = 0 to E), adjusts the
levels of Drive protective features (e.g.
Overvoltage, braking resistor turn-on,
stall prevention, etc.).
NOTE: DRIVE INPUT VOLTAGE

(NOT MOTOR VOLTAGE)
MUST BE SET IN E1-01 FOR
THE PROTECTIVE
FEATURES OF THE DRIVE
TO FUNCTION PROPERLY.
FAILURE TO DO SO MAY
RESULT IN EQUIPMENT
DAMAGE AND/OR
PERSONAL INJURY.

155.0

to

255.0

(240V)

*3

230.0 V

*3

No

Q

Q

Q

Q

Q

300H

Input
Voltage

E1-03

V/f
Pattern
Selection

Set to the type of motor being used
and the type of application.
The Drive operates utilizing a set V/F
pattern to determine the appropriate
output voltage level for each
commanded speed. There are 15
different preset V/F patterns to select
from (E1-03 = 0 to E) with varying
voltage profiles, base levels (base
level = frequency at which maximum
voltage is reached), and maximum
frequencies. There are also settings
for Custom V/F patterns that will use
the settings of parameters E1-04
through E1-13. E1-03 = F selects a
custom V/F pattern with an upper
voltage limit and E1-03 = FF selects a
custom V/F pattern without an upper
voltage limit.
0: 50Hz
1: 60Hz Saturation
2: 50Hz Saturation
3: 72Hz (60Hz Base)
4: 50Hz VT1
5: 50Hz VT2
6: 60Hz VT1
7: 60Hz VT2
8: 50Hz HST1
9: 50Hz HST2
A: 60Hz HST1
B: 60Hz HST2
C: 90Hz (60Hz Base)
D: 120Hz (60Hz Base)
E: 180Hz (60Hz Base)
F: Custom V/F
FF: Custom w/o limit

0 to FF

F

No

Q

Q

No

No

No

302H

V/F
Selection

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS
Register

Display

V/f

V/f

with

PG

Open

-loop

Vector

1

Flux

Vector

Open

Loop

Vector

2