Multi-function Contact Input Functions (H1-01 to H1-10)

„

Speed Control (ASR) Gain Adjustment for Vector Control

Use the following procedure to adjust C5-01 and C5-03 with the mechanical system and actual load con-
nected.

Setting

Value

Function

Control Methods

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

D

Speed control disable setting for V/f control with PG
OFF: Use speed control V/f control with PG
ON: Do not use speed control for V/f control with PG

No

Yes

No

No

No

E

Speed control integral reset
Enables switching between PI and P control for the speed control loop.

No

No

No

Yes

Yes

77

Speed control (ASR) proportional gain switch (switching between C5-01 and C5-03)
OFF: Use proportional gain in C5-01
ON: Use proportional gain in C5-03

No

No

No

Yes

Yes

At zero-speed, increase C5-01
(ASR P Gain 1) until there is no oscillation.

At zero-speed, decrease C5-02
(ASR I Time 1) until there is no oscillation.

Does oscillation develop when the motor
operates at the maximum normal operating
speed?

Decrease C5-01 (ASR P Gain 1).

Increase C5-02 (ASR I Time 1).

YES

NO

Adjustment completed.
(When there is higher-level position control,
adjust the position loop gain so that
overshooting/undershooting doesn’t occur.)