Speed limit (frequency reference limit function), Limiting maximum output frequency, Related parameters – Yaskawa G7 Drive User Manual

Page 247: Limiting maximum output frequency -30

Advertising
background image

6

-30

Speed Limit (Frequency Reference Limit
Function)

This section explains how to limit the motor speed.

‹

Limiting Maximum Output Frequency

If you do not want the motor to rotate above a given frequency, use parameter d2-01.

Set the upper limit value of the Drive output frequency as a percent, taking E1-04 (Maximum Output Fre-
quency) to be 100%.

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

d2-01

Frequency Ref-
erence Upper
Limit

Determines maximum frequency
reference, set as a percentage of
maximum output frequency
(E1-04). If the frequency
reference is above this value,
actual Drive speed will be limited
to this value. This parameter
applies to all frequency reference
sources.

0.0

to

110.0

100.0%

No

A

A

A

A

A

Ref Upper
Limit

Advertising