Individual functions, Using modbus communications, Modbus communications configuration – Yaskawa G7 Drive User Manual

Page 301: Communications specifications, Individual functions -84, Using modbus communications -84

Advertising
background image

6

-84

Individual Functions

This section explains the individual functions used in special applications.

‹

Using MODBUS Communications

You can perform serial communications with MEMOCON-series Programmable Controllers (PLCs) or simi-
lar devices using the MODBUS protocol.

„

MODBUS Communications Configuration

MODBUS communications are configured using 1 master (PLC) and a maximum of 31 slaves. Serial commu-
nications between master and slave are normally started by the master, and the slave responds.

The master performs signal communications with one slave at a time. Consequently, you must set the address
of each slave beforehand, so the master can perform signal communications using that address. Slaves receiv-
ing commands from the master perform the specified function, and send a response to the master.

Fig 6.54 Example of Connections between PLC and Drive

„

Communications Specifications

The MODBUS communications specifications are shown in the following table.

Item

Specifications

Interface

RS-422, RS-485

Communications Cycle

Asynchronous (Start-stop synchronization)

Communications Parameters

Baud rate:

Select from 1,200, 2,400, 4,800, 9,600, and 19,200 bps.

Data length:

8 bits fixed

Parity:

Select from even, odd, or none.

Stop bits:

1 bit fixed

Communications Protocol

MODBUS (RTU mode only)

Number of Connectable Units

31 units max. (when using RS-485)

MEMOCON-series PLC

RS-485 connections
example

Drive

Drive

Drive