Multi-function output (h2-01 to h2-05), L6-01 and l6-04 set values and lcd indications – Yaskawa G7 Drive User Manual

Page 265

Advertising
background image

6

-48

Multi-function Output (H2-01 to H2-05)

„

L6-01 and L6-04 Set Values and LCD Indications

The relationship between alarms displayed by the Digital Operator when overtorque or undertorque is
detected, and the set values in L6-01 and L6-04, is shown in the following table.

L6-06

Torque
Detection
Time 2

Sets the length of time an
Overtorque/Undertorque condition
must exist before torque detection 2
is recognized by the Drive.

0.0

to

10.0

0.1sec

No

A

A

A

A

A

Torq Det 2
Time

Set-

ting

Value

Function

Control Methods

V/f

V/f

with

PG

Open

Loop

Vec-

tor

1

Flux

Vec-

tor

Open

Loop

Vec-

tor

2

B

Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detec-
tion at ON)

Yes

Yes

Yes

Yes

Yes

17

Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at OFF)

Yes

Yes

Yes

Yes

Yes

18

Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at ON)

Yes

Yes

Yes

Yes

Yes

19

Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at OFF)

Yes

Yes

Yes

Yes

Yes

Set

Value

Function

LCD Indications

Overtorque/

Undertorque

Detection 1

Overtorque/

Undertorque

Detection 2

0

Overtorque/undertorque detection disabled.

-

-

1

Overtorque detection only with speed matching; operation continues after
overtorque (warning).

OL3 flashes

OL4 flashes

2

Overtorque detected continuously during operation; operation continues
after overtorque (warning).

OL3 flashes

OL4 flashes

3

Overtorque detection only with speed matching; output stopped upon detec-
tion (protected operation).

OL3 lit

OL4 lit

4

Overtorque detected continuously during operation; output stopped upon
detection (protected operation).

OL3 lit

OL4 lit

5

Undertorque detection only with speed matching; operation continues after
overtorque (warning).

UL3 flashes

UL4 flashes

6

Undertorque detected continuously during operation; operation continues
after overtorque (warning).

UL3 flashes

UL4 flashes

7

Undertorque detection only with speed matching; output stopped upon
detection (protected operation).

UL3 lit

UL4 lit

8

Undertorque detected continuously during operation; output stopped upon
detection (protected operation).

UL3 lit

UL4 lit

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2