Trial Operation Procedures

4-

5

‹

Basic Settings

Switch to the quick programming mode (“QUICK” will be displayed on the LCD screen) and then set the fol-
lowing user parameters. Refer to Chapter 3 Digital Operator and Modes for Digital Operator operating proce-
dures and to Chapter 5 User Parameters and Chapter 6 Parameter Settings by Function for details on the user
parameters.

Parameters that must be set are listed in Table 4.1 and those that are set according to the application are listed
in Table 4.2.

Table 4.1 Parameters that Must Be Set

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

A1-02

Control method
selection

Set the control method for the Drive.

0: V/f control
1: V/f control with PG
2: Open-loop vector control 1
3: Flux vector
4: Open-loop vector control 2

0 to 4

2

b1-01

Reference selec-
tion

Set the frequency reference input method.
0: Digital Operator
1: Control circuit terminal (analog input)
2: MODBUS communications
3: Option Card
4: Pulse train input

0 to 4

1

b1-02

Operation
method selection

Set the run command input method.
0: Digital Operator
1: Control circuit terminal (sequence input)
2: MODBUS communications
3: Option Card

0 to 3

1

C1-01

Acceleration time
1

Set the acceleration time in seconds for the output
frequency to climb from 0% to 100%.

0.0 to 6000.0

10.0 s

C1-02

Deceleration time
1

Set the deceleration time in seconds for the output
frequency to fall from 100% to 0%.

0.0 to 6000.0

10.0 s

E1-01

Input voltage set-
ting

Set the Drive's nominal input voltage in volts.

155 to 255 V

(200-240 V

class)

310 to 510 V

(380-480 V

class)

200 V

(200-240

V class)

400 V

(380-480

V class)

E2-01

Motor rated cur-
rent

Set the motor rated current.

10% to 200%

of Drive's

rated current

Setting for

general-

purpose

motor of

same

capacity
as Drive

L1-01

Motor protection
selection

Set to enable or disable the motor overload protec-
tion function using the electronic thermal relay.
0: Disabled
1: General motor protection
2: Drive motor protection
3: Vector motor protection

0 to 3

1