-34

Fig 6.31 Slip Compensation Limit

„

Selecting Slip Compensation Function During Regeneration

Set whether to enable or disable the slip compensation function during regeneration.

If the slip compensation function operates during regeneration, you might have to use the braking option
(braking resistor, Braking Resistor Unit, and Braking Unit) to momentarily increase the regenerative amount.

„

Selecting Output Voltage Limit Operation

If output voltage saturation occurs while the output voltage limit operation is disabled, the output current will
not change, but torque control accuracy will be lost. If torque control accuracy is required, change the settings
to enable the output voltage limit operation.

If the output voltage limit operation is enabled, motor magnetic flux current is controlled automatically, and
torque control accuracy is maintained to limit the output voltage references. Consequently, the output current
will increase by approximately 10% maximum (with rated load) compared with when the output voltage limit
operation is disabled, so check the Drive current margin.

Setting Precautions

If using the device at medium to low speed only, if the power supply voltage is 10% or more higher than
the motor rated voltage, or if the torque control accuracy at high speeds is insufficient, it is not necessary to
change the output voltage limit operation.

If the power supply voltage is too low compared with the motor rated voltage, torque control accuracy may
be lost even if the output voltage limit operation is enabled.

Slip compensation limit

Output frequency

E1-06: Base frequency