User Parameter Tables

5-

67

„

Fault Restart: L5

User parameters for restarting faults are shown in the following table.

L4-06

Frequency
Reference
at
Reference
Loss

If the frequency reference loss

function is enabled (L4-05=1)
and frequency reference is lost,
the Drive will run at a reduced
frequency reference
determined by the following
formula: Fref = Fref at time of
loss * L4-06.

0.0

to

100.0%

80%

No

A

A

A

A

A

4C2H

Fref at
Floss

L4-07

Torque
Limit
Control
Method
During
Accel/
Decel

Selects the control method for
the torque limit during
acceleration and deceleration.
0: Proportional Control

(integral control at fixed
speeds)

1: Normal integral control, no

need to change settings.

0 to 1

0

No

No

No

A

No

No

4C9H

Torque
Limit Sel

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L5-01

Number of
Auto
Restart
Attempts

Sets the counter for the number
of times the Drive will perform
an automatic restart on the
following faults: GF, LF, OC,
OV, PF, PUF, RH, RR, OL1,
OL2, OL3, OL4, UV1. Auto
restart will check to see if the
fault has cleared every 5ms.
When no fault is present, the
Drive will attempt an auto
restart. If the Drive faults after
an auto restart attempt, the
counter is incremented. When
the Drive operates without fault
for 10 minutes, the counter will
reset to the value set in L5-01.

0 to 10

0

No

A

A

A

A

A

49EH

Num of
Restarts

L5-02

Auto
Restart
Operation
Selection

Determines if the fault contact

activates during an automatic
restart attempt.

0: No Fault Relay - fault

contact will not activate
during an automatic restart
attempt.

1: Fault Relay Active - fault

contact will activate during
an automatic restart
attempt.

0 to 1

0

No

A

A

A

A

A

49FH

Restart Sel

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2