7

-8

CPF04

Internal

A/D Err

CPU internal A/D converter error

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the Drive.

CPF05

External

A/D Err

CPU internal A/D converter error

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the Drive.

CPF06
Option

error

Option Card connection error

The Option Card is not connected
properly.

Turn off the power and insert the
Card again.

The Drive or Option Card is faulty.

Replace the Option Card or the
Drive.

CPF07

RAM-Err

ASIC internal RAM fault

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the Drive.

CPF08

WAT-Err

Watchdog timer fault

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the Drive.

CPF09

CPU-Err

CPU-ASIC mutual diagnosis fault

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the Drive.

CPF10

ASIC-Err

ASIC version fault

The Drive control circuit is faulty

Replace the Drive.

CPF20
Option

A/D error

Communications Option Card A/D
converter error

The Option Card is not connected
properly.

Turn off the power and insert the
Card again.

The Option Card's A/D converter is
faulty.

Replace the Communications
Option Card.

CPF21
Option

CPU down

Communications Option Card self
diagnostic error

Communications Option Card fault.

Replace the Option Card.

CPF22
Option

Type Err

Communications Option Card
model code error

CPF23
Option

DPRAM

Err

Communications Option Card
DPRAM error

Table 7.1 Fault Displays and Processing (Continued)