Connection diagram, Connection diagram -2 – Yaskawa G7 Drive User Manual

Page 33

Advertising
background image

2

-2

Connection Diagram

The connection diagram of the Drive is shown in Fig 2.1.

When using the Digital Operator, the motor can be operated by wiring only the main circuits.

Fig 2.1 Connection Diagram (Model CIMR-G7U2018 Shown Above)

T/L3

S/L2

R/L1

S3

(H1-01)

S2

S1

SC

E(G)

S4

(H1-02)

S5

(H1-03)

S6

(H1-04)

S7

(H1-05)

SN

S+

R-

R+

S-

IG

G7

W/T3

V/T2

U/T1

MC

MB

MA

M2

M1

M4

M3

E(G)

(H4-01) FM

(H4-04) AM

AC

(H2-01)

(H2-02)

Modbus RTU

Communications

RS-485/422

19.2 Kbps

External

Frequency

Reference

MCCB

L3

L2

L1

3-Phase

Power Supply

50/60Hz

Reverse Run/Stop

Foward Run/Stop

Multi-function

Digital Inputs
24VDC, 8mA

M

Motor

Digital Output 1

Fault Contact

250VAC, 30VDC, 1A

Multi-function

Digital Outputs 2-4

250VAC, 30VDC, 1A

+

-

+

-

Terminating

Resistor

S8

(H1-06)

M6

M5

(H2-03)

Digital Inputs
24VDC, 8mA

SP +24VDC

+V +15VDC +/-10%, 20mA

AC

2k

Ω

RP 0 to 32kHz, 5 to 12VDC, 3k ***
Multi-function Pulse Input

(H6-01)

S1-1

-V -15VDC +/-10%, 20mA

Ω

(H6-06) MP

S9

(H1-07)

S10

(H1-08)

S11

(H1-09)

S12

(H1-10)

C3

P3

(H2-04)

P4

(H2-05)

C4

Multi-function

Digital Outputs 5-6

48VDC, 50mA

+ 1

+ 2

+ 3

-

Shorting Bar Standard:
CIMR-G7U20P4 to 2015
CIMR-G7U40P4 to 4015

DC Link Choke
Standard:
CIMR-G7U2018 to 2110
CIMR-G7U4018 to 4300

U

X

Remove if adding
external DC link
choke

B1

B2

Jumper CN15

V

CH1
CH2

DIP Switch S1

S1-1

OFF

ON

S1-2

T/L31

S/L21

R/L11

Remove jumpers if
using 12 pulse input

2k

Ω

Ω

A3 0 to +/-10VDC, 20k *
Multi-function Analog Input 2

(H3-05)

A1 0 to +/-10VDC, 20 k *

Ω

110

Ω

* +/-11 Bit Resolution, 0.2% Accuracy

** 10 Bit Resolution, 0.2% Accuracy
*** +/-1% Accuracy

See Page 2-25 for details.

A2 4 to 20mA, 250 *
[0 to +/-10VDC, 20k **]
Multi-function Analog Input 1

(H3-09)

Ω

Ω

(S1-2 ON)

(S1-2 OFF)

Output Frequency

T1
T2
T3

Branch circuit
protection supplied
by others.

Fault Reset

External Fault

Multi-Step Reference2

Multi-Step Reference1

Baseblock

Jog Reference

Fast-Stop N.O.

Accel / Decel Time 1

Multi-Step Reference4

Multi-Step Reference3

During Run

Zero Speed

Frequency Agree 1

Inverter Ready

Minor Fault - Alarm

Output Current

Multi-function
Analog Output 1 - 2
0 to +/-10VDC, 2mA
4-20mA, 500
+/-9 Bit Resolution
+/- 8% Accuracy

Ω

Output Frequency

Multi-function
Pulse Output
0 to 32kHz
9VDC @ 3k
+/-1% Accuracy

Ω

+

12 Pulse Input Terminals R1/L11, S1/L21, T1/L31 are standard
on CIMR-G7U2018 - 2110 and CIMR-G7U4018 - 4300.

External Braking Terminal 3 is standard on CIMR-G7U2018
- 2110 and CIMR-G7U4018 - 4300.

Braking Terminals B1, B2 are standard on CIMR-G7U20P4 -
2015 and CIMR-G7U40P4- 4015.

Advertising