Yaskawa G7 Drive User Manual

Page 158

Advertising
background image

User Parameter Tables

5-

47

„

Digital Output Card (DO-02 and DO-08): F5

User parameters for the Digital Output Card are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

F5-01

DO-02/
DO-08
Channel 1
Output
Selection

Sets the digital output
function number for channel 1.
See the H2 parameter group
for possible selections.
Enabled when digital output
card DO-02 or DO-08 is used.

0 to 37

0

No

A

A

A

A

A

399H

DO Ch1
Select

F5-02

DO-02/
DO-08
Channel 2
Output
Selection

Sets the digital output
function number for channel 2.
See the H2 parameter group
for possible selections.
Enabled when digital output
card DO-02 or DO-08 is used.

0 to 37

1

No

A

A

A

A

A

39AH

DO Ch2
Select

F5-03

DO-08
Channel 3
Output
Selection

Sets the digital output
function number for channel 3.
See the H2 parameter group
for possible selections.
Enabled when digital output
card DO-02 or DO-08 is used.

0 to 37

2

No

A

A

A

A

A

39BH

DO Ch3
Select

F5-04

DO-08
Channel 4
Output
Selection

Sets the digital output
function number for channel 4.
See the H2 parameter group
for possible selections.
Enabled when digital output
card DO-02 or DO-08 is used.

0 to 37

4

No

A

A

A

A

A

39CH

DO Ch4
Select

F5-05

DO-08
Channel 5
Output
Selection

Sets the digital output
function number for channel 5.
See the H2 parameter group
for possible selections.
Enabled when digital output
card DO-02 or DO-08 is used.

0 to 37

6

No

A

A

A

A

A

39DH

DO Ch5
Select

F5-06

DO-08
Channel 6
Output
Selection

Sets the digital output
function number for channel 6.
See the H2 parameter group
for possible selections.
Enabled when digital output
card DO-02 or DO-08 is used.

0 to 37

37

No

A

A

A

A

A

39EH

DO Ch6
Select

F5-07

DO-08
Channel 7
Output
Selection

Sets the digital output
function number for channel 7.
See the H2 parameter group
for possible selections.
Enabled when digital output
card DO-02 or DO-08 is used.

0 to 37

0F

No

A

A

A

A

A

39FH

DO Ch7
Select

Advertising