Yaskawa G7 Drive User Manual

Page 357

Advertising
background image

6

-140

o2-01

Local/Remote
Key Function
Selection

Determines if the Digital

Operator Local/Remote key is
functional.

0: Disabled
1: Enabled

0 to 1

1

No

A

A

A

A

A

Local/Remote
Key

o2-02

STOP Key
Function
Selection

Determines if the STOP key on

the Digital Operator will stop the
Drive when Drive is operating
from external terminals or serial
communication.

0: Disabled
1: Enabled

0 to 1

1

No

A

A

A

A

A

Oper STOP
Key

o2-03

User Parameter
Default Value

Allows storing of parameter
settings as a User Initialization
Selection.
0: No Change
1: Set Defaults - Saves current
parameter settings as user
initialization. A1-03 now allows
selecting <1110> for user
initialization and returns o2-03 to
zero.
2: Clear All - Clears the currently
saved user initialization. A1-03
no longer allows selecting <1110>
and returns o2-03 to zero.

0 to 2

0

No

A

A

A

A

A

User Defaults

o2-05

Frequency
Reference
Setting Method
Selection

Determines if the Data/Enter key
must be used to input a frequency
reference from the Digital
Operator.
0: Disabled - Data/Enter key must
be pressed to enter a frequency
reference.
1: Enabled - Data/Enter key is not
required. The frequency reference
is adjusted by the up and down
arrow keys on the Digital
Operator without having to press
the data/enter key.

0 to 1

0

No

A

A

A

A

A

Operator
M.O.P.

o2-07

Cumulative
Operation Time
Setting

Sets the initial value of the
elapsed operation timer U1-13.

0

to

65535

0 hr

No

A

A

A

A

A

Elapsed Time
Set

o2-10

Cumulative
Cooling Fan
Operation Time
Setting

Sets the initial value of the
heatsink fan operation time
monitor U1-40.

0

to

65535

0 hr

No

A

A

A

A

A

Fan ON Time
Set

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2