Machine Protection

6-

47

L6-03

Torque
Detection
Time 1

Sets the length of time an
Overtorque/Undertorque condition
must exist before Torque Detection
1 is recognized by the Drive.

0.0

to

10.0

0.1sec

No

A

A

A

A

A

Torq Det 1
Time

L6-04

Torque
Detection
Selection 2

Determines the Drive's response to
an Overtorque/Undertorque
condition. Overtorque and
Undertorque are determined by the
settings in parameters L6-05 and
L6-06. The multi-function output
settings "18" and "19" in the H2-oo
parameter group are also active if
programmed.
0: Disabled
1: OL4 at Speed Agree - Alarm

(Overtorque Detection only
active during Speed Agree and
Operation continues after
detection).

2: OL4 at RUN - Alarm

(Overtorque Detection is always
active and operation continues
after detection).

3: OL4 at Speed Agree - Fault

(Overtorque Detection only
active during Speed Agree and
Drive output will shut down on
an OL4 fault).

4: OL4 at RUN - Fault (Overtorque

Detection is always active and
Drive output will shut down on
an OL4 fault).

5: UL4 at Speed Agree - Alarm

(Undertorque Detection is only
active during Speed Agree and
operation continues after
detection).

6: UL4 at RUN - Alarm

(Undertorque Detection is always
active and operation continues
after detection).

7: UL4 at Speed Agree - Fault

(Undertorque Detection only
active during Speed Agree and
Drive output will shut down on
an OL4 fault).

8: UL4 at RUN - Fault

(Undertorque Detection is always
active and Drive output will shut
down on an OL4 fault).

0 to 8

0

No

A

A

A

A

A

Torq Det 2
Sel

L6-05

Torque
Detection
Level 2

Sets the Overtorque/Undertorque
detection level as a percentage of
Drive rated current or torque for
Torque Detection 2. Current
detection for A1-02 = 0 or 1. Torque
detection for
A1-02 = 2 or 3.

0

to

300

150%

No

A

A

A

A

A

Torq Det 2
Lvl

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2