Related parameters – Yaskawa G7 Drive User Manual

Page 303

Advertising
background image

6

-86

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b1-01

Frequency
Reference
Selection

Selects the frequency reference
input source.
0: Operator - Digital preset speed

U1-01 or d1-01 to d1-17.

1: Terminals - Analog input

terminal A1 (or terminal A2
based on parameter H3-09).

2: Serial Com - Modbus RS-422/

485 terminals R+, R-,

S+, and S-.
3: Option PCB - Option board

connected on 2CN.

4: Pulse Input (Terminal RP)

0 to 4

1

No

Q

Q

Q

Q

Q

Reference
Source

b1-02

Run
Command
Selection

Selects the run command input

source.

0: Operator - RUN and STOP

keys on Digital Operator.

1: Terminals - Contact closure on

terminals S1 or S2.

2: Serial Com - Modbus RS-422/

485 terminals R+, R-,

S+, and S-.
3: Option PCB - Option board

connected on 2CN.

0 to 3

1

No

Q

Q

Q

Q

Q

Run Source

H5-01

Drive Node
Address

Selects Drive station node number
(address) for Modbus terminals
R+, R-, S+, S-. The Drive's power
must be cycled for the setting to
take effect.

0 to 20

*

1F

No

A

A

A

A

A

Serial Comm
Adr

H5-02

Communicati
on Speed
Selection

Selects the baud rate for Modbus
terminals R+, R-, S+ and S-. The
Drive's power must be cycled for
the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps

0 to 4

3

No

A

A

A

A

A

Serial Baud
Rate

H5-03

Communicati
on Parity
Selection

Selects the communication parity

for Modbus terminals R+, R-, S+
and S-. The Drive's power must be
cycled for the setting to take
effect.

0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

No

A

A

A

A

A

Serial Com
Sel

H5-04

Stopping
Method After
Communicati
on Error

Selects the stopping method when
a communication timeout fault
(CE) is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

No

A

A

A

A

A

Serial Fault